Subcooling calculatorSC
Take pressure and temperature at the same spot on the liquid line near the outdoor service valve, unit running 10–15 min, clean coils. Blends (R-454B) use the bubble point for subcooling.
Superheat calculatorSH
Target superheat (piston systems)
Blends use the dew point for superheat. Piston target uses the common field formula (3 × WB − 80 − outdoor DB) ÷ 2; if it comes out under 5°F, don't charge by superheat (check airflow/conditions). TXV systems: charge by subcooling; superheat usually lands about 8–12°F at the outdoor unit.
PT chart lookupPT
Range −40°F to 150°F. R-454B shows both bubble (liquid, for subcooling) and dew (vapor, for superheat). Data: Chemours Freon/Opteon PT data; R-410A, R-32, R-22 checked against the Chemours A/C PT guide within 0.1 psi.
Check TD (temperature split)ΔT
How to measure
- Run 10–15 min. Return: at the return grille/plenum before the filter. Supply: in the supply plenum or first trunk, out of line of sight of the coil/strips (radiant heat reads high).
- Low cooling TD: low charge, restriction, too much airflow, high humidity (more latent load), or bad compressor/valves.
- High cooling TD: low airflow (dirty filter/coil, blower speed, closed or undersized ducts), very dry air, iced coil starting.
Cooling ranges are field rules of thumb (about 16–22°F at ~50% RH; lower split in humid air). The manufacturer's target-split chart rules.
Condenser & evaporator splitCTOA
CTOA = condensing temp over ambient. High CTOA: dirty condenser, bad fan, recirculating air, overcharge, non-condensables. Low CTOA: undercharge or weak compressor. Evaporator TD (return air minus evaporator saturation temp) is usually about 35°F at ~400 CFM/ton. Rules of thumb only; the maker's data comes first.
Airflow (CFM)CFM
By tonnage
Temperature-rise method (electric strips)
CFM = (volts × amps × 3.413) ÷ (1.08 × ΔT). Run strips only (compressor off), measure total heater amps and supply − return after temps settle. Includes the blower's own heat, so it reads slightly high. 1.08 is for sea-level air.
Capacitor testµF
Running check (under load)
Safe bench test, step by step
- Kill power at the disconnect and verify 0 V with your meter.
- Discharge the cap: a 20 kΩ / 5 W resistor (or insulated discharge tool) across C–HERM and C–FAN. No screwdriver shorting.
- Photo the wiring, then pull the wires off the cap.
- Meter on capacitance (µF). Dual run cap: C to HERM = compressor section (large value), C to FAN = fan section (small value, e.g. 45/5).
- Compare each to the rating ± tolerance on the label. Replace if out of range, bulged/domed top, leaking oil, or burnt terminals.
- Replace with the same µF and the same or higher voltage (370 V → 370 or 440 V OK).
Motor / compressor ampsA
Clamp meter, step by step
- Set the clamp to AC amps. Clamp one conductor only (two legs together cancel out).
- Compressor: clamp the C (common) wire for total compressor amps. Fan motor: clamp its common lead.
- Let it run 10+ min, then compare to the nameplate (data plate on the unit / motor label). Read voltage at the same time.
- Startup: use inrush/max mode. Near LRA for more than a second or two = locked rotor / hard start.
RLA is a rating, not a target. Normal running amps are usually below RLA and change with load, voltage and outdoor temp.
Breaker & wire size (MCA / MOCP)NEC
| Copper THHN/THWN | 60°C | 75°C |
|---|---|---|
| 14 AWG | 15 | 20 |
| 12 AWG | 20 | 25 |
| 10 AWG | 30 | 35 |
| 8 AWG | 40 | 50 |
| 6 AWG | 55 | 65 |
| 4 AWG | 70 | 85 |
| 3 AWG | 85 | 100 |
| 2 AWG | 95 | 115 |
Ampacity from NEC Table 310.16 (copper, ≤3 current-carrying conductors, 30°C ambient). Use the 60°C column unless every termination is rated 75°C (NEC 110.14(C)). Breaker must not exceed MOCP; if MOCP isn't a standard size, go down. Article 440 lets A/C wire be protected above the 14/12/10 AWG small-conductor limits, up to MOCP. Long runs, rooftop heat, aluminum and local code change the answer; follow the AHJ.
Contactor checkV
- Coil: with a call for cooling, read 24 VAC across the coil terminals. 24 V present but no pull-in = bad coil. No 24 V = control side (thermostat, float switch, pressure switch, board).
- Voltage drop: unit running, measure line to load on each pole (L1–T1, L2–T2). Should be near 0 V; under about 0.5 V is fine. More than ~1 V, or pitted/burnt contacts = replace.
- Power off: look for pitted contacts, ants/bugs, melted housing, loose lugs. Check line voltage is within ±10% of nameplate.
Insulation (megohm) & blower motorMΩ
Megohm (insulation) test
- Power off, wires off the compressor terminals. Never megger a compressor in a vacuum, and never through an inverter drive or control board.
- 500 V (or 1000 V per tool/maker) from each terminal to a clean copper line or ground lug.
- Common field guide: 100 MΩ+ good · 20–100 MΩ watch (moisture/oil, retest) · under 20 MΩ problem · near 0 = grounded. Compressor makers' limits come first.
Blower motor
- PSC: check run cap (µF) and amps vs FLA; check winding ohms for opens/grounds; spin by hand for tight bearings.
- ECM/X13: confirm 120/240 V line power always present, then 24 V on the tap/speed terminal on a call. Line + signal but no run = motor/module (follow the maker's motor test tool/procedure).
- High amps + low airflow: dirty wheel, restricted filter/ducts, wrong speed tap.
Winding resistance checkΩ
Single-phase PSC/CSR compressors. Typical: C–R lowest, C–S middle, S–R highest and equal to C–S + C–R. Use a good meter on the low Ω range, zero the leads, and compare to the maker's spec when you have it. Three-phase scrolls: all three readings should match within ~5–10%.
Checking a compressor, step by stepGuide
1. Identify terminals
Look for C/S/R on the terminal cover or fusite. If unmarked, measure all three pairs: the highest reading is S–R, so the terminal left out is C. From C, the lowest reading goes to R (run), the middle to S (start).
2. Winding resistance
Power off, discharged cap, wires off. S–R should equal C–S + C–R. An infinite reading = open winding; near 0 or much lower than spec = shorted winding.
3. Short to ground
Meter on highest Ω (or a megohmmeter, see Electrical tab) from each terminal to clean copper (scrape the paint). Any reading on a standard ohmmeter = grounded compressor, replace. Check the breaker hasn't been tripping.
4. Open internal overload
C–R and C–S both OL but S–R reads = internal overload open (it's in the common). If the shell is hot, let it cool (can take 1–3+ hours; a wet rag or water mist speeds it up). Then find why it overheated: low charge, bad cap, high head, low voltage, short cycling.
5. Amp draw
Clamp the C wire. Running amps at or under RLA is normal; climbing well over RLA = high head, bad run cap, low voltage, mechanical wear. Reading near LRA and tripping the overload = locked rotor.
6. Locked rotor / hard start
Test the run cap first. Check voltage at the compressor during startup (sag below ~10% under nameplate hurts starts). A hard start kit (start cap + relay, sized to the compressor) can get a tight compressor going; if it still won't start with good cap, good voltage and balanced pressures, the compressor is mechanically stuck.
7. Pressures / valve check
Running with good airflow and charge: low head + high suction and amps below normal = worn valves/scroll not pumping (internal bypass). Pressures that equalize fast at shutdown also point to leaking valves. Scrolls running backwards (3-phase) are loud with no pressure difference; swap two legs.
Quick troubleshooting flow
| Symptom | Check in this order |
|---|---|
| Won't start, silent | Breaker/disconnect · 24 V to contactor coil (thermostat, float switch, pressure/safety switches, board delay) · contactor pulled in? · line volts at compressor · open overload (hot shell) · open winding |
| Hums, won't run | Run cap (C–HERM) · voltage under load · one contactor pole burnt (single-phasing) · try hard start kit · locked rotor (amps near LRA) |
| Trips breaker | Short to ground (megohm/ohm to copper) · shorted winding · bad wiring/lugs · undersized breaker vs MOCP · locked rotor |
| Runs, no cooling | Pressures vs PT (SH/SC) · amps low? · low head + high suction = valves · charge/leak · restriction (high SC, high SH) · outdoor fan · reversing valve on heat pumps |
| Short cycles | Internal overload (hot) · high/low pressure switch · thermostat location · oversized unit · bad cap |
Thermostat wire colors24V
| Term. | Usual color | What it does |
|---|---|---|
| R / Rh / Rc | Red | 24 V hot from transformer (Rh heat, Rc cool) |
| C | Blue or black | 24 V common (powers the thermostat) |
| Y / Y1 | Yellow | Compressor / cooling stage 1 |
| Y2 | Light blue / other | Compressor stage 2 |
| G | Green | Indoor fan |
| W / W1 | White | Heat (furnace/strips on straight A/C) |
| W2 / AUX | Brown / other | 2nd stage or auxiliary heat strips |
| E | Varies | Emergency heat (strips only, compressor locked out) |
| O/B | Orange (O) / dark blue (B) | Reversing valve. O = energized in cooling (most brands: Carrier, Trane, Goodman, Lennox). B = energized in heat (Rheem/Ruud, some older units). |
Colors are custom, not code. Always trace the wire to the terminal at the air handler/furnace board.
Condensate drain & float switchDrain
- No cooling but indoor fan runs or nothing runs: check the float switch (in the secondary pan, on the primary drain or in the condensate pump). Most open the R or Y circuit when tripped.
- Read 24 V across the float switch: 24 V across it = switch open (tripped or bad). 0 V with power present = closed.
- Clear the line: wet-vac at the outside end, or flush from the cleanout/vent tee. Check the trap (required on draw-through air handlers) and slope (about 1/8" per foot).
- Condensate pump: lift the float to test, check the check valve and discharge tube for slime; confirm the pump's safety switch is wired.
- Prevention: drain tabs/treatment per maker, clean pan, and don't let the vent get capped. Find out why it clogged (algae is common in South Florida).
Heat pump defrost checkHP
- Heat mode, coil frosted. Check the defrost board settings (commonly 30/60/90 min run time between checks) and the coil sensor/thermostat clipped tight on the right tube.
- Many boards have TEST pins: jumper them briefly (per the board label) to force defrost.
- In defrost: reversing valve shifts to cooling, outdoor fan stops, aux heat (W2) usually comes on, steam off the coil. It should end on coil temperature or a max time (often about 10 min).
- No shift: check 24 V to the reversing valve solenoid (O/B), solenoid coil ohms, and whether the valve is stuck (temperatures on the 4 lines).
- Coil sensor: compare to the maker's resistance-vs-temp chart; a sensor reading "warm" will never start defrost.
Fault / blink codesCodes
- Read the LED flash code with the door safety switch held in (don't count while the door is off and the board resets). Many boards also store the last codes; check before cycling power.
- Look up the code on the label inside the panel door or the board's service manual for that exact model. The same flash count means different things on different brands and boards, so we don't list generic codes here.
- Inverter/communicating systems (Carrier Infinity, Trane ComfortLink, Daikin, mini-splits): use the thermostat's service menu or the maker's app/tool for the fault history.
- Fix the cause, not just the code: a pressure-switch or limit code is a symptom (airflow, venting, charge).
Check order = most likely first. "Rule of thumb" values are typical field numbers; the manufacturer's data comes first.
Pressure diagnosis matrixP/T
Compare suction/head to what's normal for the conditions (PT chart, CTOA, evap TD). Confirm with superheat (SH) and subcooling (SC). Rule of thumb.
| Low head | High head | |
|---|---|---|
| Low suction | Undercharge/leak (SH high, SC low) · low indoor airflow (SH low) · cold outdoor temps | Restriction at drier/metering device (SH high, SC high) · overcharge plus low airflow |
| High suction | Compressor not pumping: worn valves/scroll, internal bypass (amps low) · leaking reversing valve (HP) · TXV stuck open (SH low) | Overcharge (SC high, SH low) · dirty condenser/fan out (SC normal) · noncondensables · very high indoor load |
Charge problems at a glance
| Problem | SH | SC | Suct. | Head | Amps |
|---|---|---|---|---|---|
| Undercharge | ↑ | ↓ | ↓ | ↓ | ↓ |
| Overcharge | ↓* | ↑ | ↑ | ↑ | ↑ |
| Restriction (drier/meter) | ↑ | ↑ | ↓ | – / ↓ | ↓ |
| Low indoor airflow | ↓ | – / ↑ | ↓ | ↓ | ↓ |
| Dirty condenser / fan | – | – / ↓ | ↑ | ↑ | ↑ |
| Noncondensables | – | – / ↑ | ↑ | ↑↑ | ↑ |
| Weak compressor | ↑ / – | ↓ | ↑ | ↓ | ↓ |
* On TXV systems, superheat stays near normal with over/undercharge until it's severe; judge TXV charge by subcooling. – = about normal.
Not cooling / blowing warm airCool
- Thermostat in COOL, setpoint below room temp, fan AUTO. Batteries/blank screen?
- Filter and indoor coil: dirty filter or iced coil? (see Frozen coil)
- Outdoor unit running? Compressor and fan both? If not → "Outdoor unit not running".
- Measure TD across the coil (16–22°F typical, rule of thumb).
- Gauges: suction, head, SH, SC. Use the matrix above.
- Compressor amps vs RLA. Low amps + warm suction line = not pumping or low charge.
Likely causes: bad capacitor → dirty filter/coil → low charge/leak → contactor → dirty condenser → compressor/valves → heat pump reversing valve stuck in heat.
Unit won't turn on (nothing runs)Power
- Thermostat screen on? Blank = no 24 V (or dead batteries on battery stats).
- Breakers for the air handler/furnace and condenser; furnace/air handler service switch.
- Blower door switch pushed in (door on).
- Float switch tripped? Water in the secondary pan or drain backed up (see Water leaking).
- Line voltage into the air handler (120 or 240 V per nameplate).
- Transformer: 24 V on secondary (R to C). Line in but no 24 V out = bad transformer.
- Low-voltage fuse on the board (often 3 or 5 A). Blown = look for a short: chafed thermostat wire, outdoor wire on the line set, shorted contactor coil.
- Outdoor disconnect fuses/pull-out.
Likely causes: tripped float switch → blown 3/5 A fuse (shorted wire) → tripped breaker → door switch → bad transformer → thermostat.
Indoor runs, outdoor unit doesn'tCond.
- Outdoor disconnect and breaker. Line voltage at the contactor line side.
- Contactor pulled in? Measure 24 V at the coil on a call.
No 24 V: Y wire broken, high/low pressure switch open, float switch in Y, board/time delay (wait 5 min), thermostat. - Contactor in but nothing runs: burnt contacts, voltage on load side?
- Humming / fan or compressor tries: test the capacitor (C–HERM, C–FAN).
- Compressor hot and silent: internal overload open; let it cool.
- Compressor near LRA and won't start with good cap/voltage: try a hard start kit, then condemn.
Likely causes: bad run capacitor → contactor (pitted, ants) → broken Y/C wire → open pressure switch → tripped breaker → compressor.
Outdoor fan not spinningFan
- Power off. Spin the blade with a stick: stiff or grinding = bearings.
- Test the FAN side of the capacitor (C–FAN).
- Power on: voltage at the fan leads (from contactor/board). Some units run the fan from a defrost board (heat pumps).
- Motor amps vs FLA; motor hot and shut off = thermal overload, replace if it repeats.
- Motor windings: open = replace. Check blade set-screw slipping on the shaft.
Likely causes: fan side of cap → seized motor bearings → bad motor → defrost board relay (HP) → slipping blade.
Spinning it by hand to start it proves a bad cap or weak motor. Don't leave it that way: the compressor overheats with no condenser fan.
Compressor won't start / hums / trips breakerComp
- Voltage at compressor terminals on a call (both legs; single-phasing from a burnt contactor pole).
- Run cap C–HERM in tolerance.
- Winding ohms C–S, C–R, S–R and each to ground (Compressor tab).
- Amps at startup: near LRA = locked rotor. Try a hard start kit sized to the compressor.
- Trips breaker instantly = short to ground or shorted winding (megohm test). Trips after running = high amps (high head, low voltage) or weak breaker.
- Restarting on high pressures right after shutoff: needs the 3–5 min time delay to equalize (pistons equalize, non-bleed TXVs may not).
Likely causes: bad run cap → open overload (hot) → contactor/single-phasing → low voltage → locked rotor → grounded/shorted winding.
Frozen evaporator / iced suction lineIce
- Shut cooling off, run fan ON to thaw (or heat). Protect against overflow while it melts. Never chip ice.
- Airflow first: filter, dirty coil, blower speed/wheel, closed registers, crushed flex, return too small. Check static pressure.
- After thaw: SH/SC. Low suction with high SH = undercharge; low suction with low SH = airflow.
- Blower running all the time? Running at night in mild weather with low load, oversized unit.
- Restriction at the metering device (frost starts right after the TXV/piston).
Likely causes: dirty filter → low airflow (blower, ducts, coil) → low charge → restriction → thermostat set very low on mild nights.
Water leaking / clogged drain / panWater
- Kill the unit if water is in the secondary pan/ceiling. Check the float switch tripped (good) or bypassed (bad).
- Clear the primary drain: wet-vac at the outside end, flush at the cleanout tee. Check the trap and slope (about 1/8" per foot).
- Primary pan rusted through or cracked (common on older units) = water in secondary pan even with clear drain.
- Coil icing then melting causes overflow, so check airflow/charge too.
- Sweating: uninsulated suction line, supply plenum/boot sweating in hot attic, missing duct insulation, air handler cabinet panel gaps.
- Condensate pump: float stuck, check valve slimed, tubing kinked.
Likely causes: algae-clogged drain → missing/blocked trap → rusted pan → frozen coil melting → sweating ducts/lines → pump failure.
Short cyclingCycle
- How long on/off? Under ~5–10 min on is short (rule of thumb).
- Is it the whole system or only the compressor (outdoor shuts off, indoor keeps going)?
- Compressor only: hot compressor/internal overload, high or low pressure switch tripping (dirty condenser, low charge), bad cap.
- Whole system: thermostat near a supply register/sunny wall, loose wire, cycle-rate setting, float switch flickering.
- Oversized system: cools fast, leaves humidity high. Heat: limit switch tripping from low airflow.
Likely causes: safety/pressure switch trips (dirty condenser, charge) → overload on hot compressor → thermostat location/wiring → oversized unit → float switch.
Long run times / not reaching setpointRun
- Check TD and outdoor temp. On extreme days, a properly sized unit may run all afternoon (design is about 75°F inside at local design temp, e.g. ~92°F in South Florida).
- Filter, indoor coil, condenser coil cleanliness.
- Charge (SH/SC), compressor amps, CTOA.
- Duct leaks / disconnected duct in attic (big hot spot in return = attic air pulled in).
- Load: windows, insulation, attic ventilation, number of people, setpoint very low.
- Two-stage/variable unit: is it staying in low stage?
Likely causes: dirty coils/filter → low charge → duct leakage → undersized system or heat load → weak compressor.
High indoor humidityRH
- Measure indoor RH (target roughly 40–55%, rule of thumb).
- Fan set to ON instead of AUTO? Re-evaporates water off the coil. Set to AUTO.
- Airflow too high for the climate: set ~350 CFM/ton or enable dehumidify mode (ECM).
- Oversized unit short-cycling; coil never gets cold long enough.
- Low charge raises coil temp, so it removes less moisture.
- Return leaks pulling attic/humid air; bath/kitchen exhaust; open windows/doors.
- Still high after all that: whole-home dehumidifier.
Noises and what they meanNoise
| Noise | Likely causes |
|---|---|
| Buzz / hum | Contactor coil chatter (low 24 V, bugs), compressor/fan trying to start (cap), loose panel, transformer |
| Rattle | Loose panel screws, debris in condenser fan, fan blade hitting, loose blower wheel, compressor mounts, line set touching |
| Squeal / screech | Motor bearings (blower or condenser fan), belt (older units); scroll compressor high-pitch whine on shutdown can be normal for a few seconds |
| Hiss | Refrigerant leak, TXV under load (often normal), duct leaks, high static at grilles |
| Bang / clunk | Compressor internal failure or loose mount, blower wheel off, ductwork oil-canning (pressure) |
| Click (repeating) | Relay or contactor cycling, thermostat/board issue, short cycling |
| Gurgle | Drain trap empty or partly clogged; refrigerant flash (low charge) |
OdorsSmell
- Burning / electrical: shut off. Overheated motor, burnt wires/terminals, strip heat dust on first use (brief, normal).
- Musty / dirty sock: mold/bacteria on coil, pan, wet duct liner or standing water in the drain pan.
- Rotten egg (gas furnace): possible gas leak. Leave, call the gas utility.
- Sewage: drain trap dry or drain tied into sewer without a proper trap.
- Chemical / sweet: refrigerant leak can smell faintly sweet or oily; check for oil spots.
- Dead animal: rodent in ducts/return; also lizards/frogs in air handler.
High electric bills$
- Run time and setpoint: compare to last year same month and weather.
- Heat pumps: aux/emergency strip heat running too much (check W2 and strip amps).
- Dirty coils/filter, low charge (long run times), failing compressor (high amps).
- Duct leaks to attic, especially returns.
- Old low-SEER equipment, oversizing, fan left ON.
- Not the A/C: water heater, pool pump, other loads. Check with a clamp meter at the panel.
One room hot / airflow problemsAir
- Registers open, dampers set, nothing blocking returns.
- Attic: crushed, kinked or disconnected flex; long runs; supply boot pulled off.
- Total external static (TESP): manometer between return (after filter, before blower) and supply (after coil). Most residential air handlers/furnaces are rated around 0.5 in WC total (check the nameplate/blower table). Above rating = restricted ducts, filter or coil.
- Filter drop: high-MERV or dirty filters add a lot of static.
- Room has no return or door is closed: add a jumper/transfer grille.
- Blower speed tap / ECM settings match tons (≈400 CFM/ton).
- Duct leakage: feel/smoke-test joints, mastic seal; duct blaster test for numbers.
Low charge / leak searchLeak
Low SC + high SH + low pressures = low charge. A system doesn't use refrigerant: find the leak before adding.
- Look: oily spots at flares, Schrader cores, service valves, braze joints, coil U-bends, rubbing lines.
- Electronic detector: heated diode or infrared, A2L-rated for R-454B/R-32. Move slowly (~1 in/sec), below the joint (refrigerant is heavier than air), fan off.
- Bubble solution: confirm the exact spot.
- Nitrogen pressure test: recover charge, pressurize with dry nitrogen (with regulator) to the maker's test pressure, never above the low-side rating on the nameplate. Watch for drop and bubble-test. Isolate sections (indoor coil vs line set vs outdoor).
- UV dye: only dye approved by the compressor maker; find with UV light later.
- Schrader cores: replace, cap with O-ring caps.
Never pressurize with oxygen or compressed air. EPA 608 rules apply to leak repair.
Restriction diagnosisRestr.
- Signs: low suction, high SH, normal to high SC, low amps.
- Filter drier: temperature in vs out. More than about 3°F drop (rule of thumb) or sweating/frost at the outlet = restricted.
- Kinked or flattened liquid line: frost or cold spot at the kink.
- Piston: wrong size or debris; frost right after it.
- TXV: hunting = SH swinging up and down (bulb placement/insulation, low charge, oversized valve). Stuck closed / lost bulb charge = high SH, low suction even with full charge; warm bulb in hand should open it. Stuck open / overfeeding = low SH, floodback.
- Check the TXV bulb: clamped at 10–2 o'clock on a horizontal suction line, insulated.
Noncondensables (air in the system)NC
- Signs: high head and high CTOA with a clean condenser, good fan and correct charge; often high amps.
- Standing test: unit off long enough that the outdoor coil and refrigerant are at outdoor temp. Pressure should match the PT chart for that temp. Clearly higher = noncondensables (or wrong/mixed refrigerant).
- Fix: recover the charge, replace the drier, pull a deep vacuum (500 microns or lower with a decay test, per maker), weigh in a fresh charge.
Heat pump not heating / defrost / reversing valveHP
- Thermostat set to HEAT, configured for heat pump, O vs B set right for the brand (blowing cold in heat = often O/B wrong).
- Outdoor unit running? Same checks as cooling (cap, contactor).
- Reversing valve: check 24 V at the solenoid when it should shift, coil ohms, and touch-test the lines. In heat the large line to the indoor coil is hot. Valve stuck halfway = warm suction, poor capacity both modes.
- Tap the valve body lightly / cycle it under pressure if stuck; replace if it won't shift.
- Stuck in defrost (fan off, steam, cold air): bad defrost board/relay or sensor. Check the coil sensor resistance vs chart and the board's terminate signal.
- Iced solid outdoor coil: defrost not starting. Force with TEST pins; check sensor and board.
- Low charge reduces heat output a lot. Check charge in cooling or by the maker's heat-mode chart.
Electric strip heat not workingStrips
- Separate breaker(s) for the heat kit on and not tripped.
- 24 V on W (or W2/AUX) from the thermostat on a heat call.
- Sequencer or relay: 24 V on the coil, then line voltage passing through to each element.
- High limit (auto-reset) and thermal fuse/link (one-shot): power off, ohm across each; open = tripped/failed. Find why: low airflow, dirty filter.
- Element ohms: R = V² ÷ W. Example 5 kW at 240 V → 11.5 Ω. OL = broken element.
- Amps on each element: about W ÷ V (5 kW at 240 V ≈ 20.8 A).
Blower not runningBlower
- Thermostat G call: 24 V at G on the board. Door switch closed.
- PSC: line voltage at the speed tap and common. Present but no run: test the run cap, spin the wheel for tight bearings, winding ohms.
- ECM (constant torque, X13): constant line voltage always at the 5-pin plug, plus 24 V on a speed tap on a call. Both present, no run = motor/module.
- Variable-speed ECM: needs line power and board signals; use the maker's test tool or a motor tester. Modules can be replaced separately on some models.
- Never unplug/plug an ECM's power with power on; wait for capacitors to discharge (about 5 min) before working on the module.
Thermostat issuesTstat
- Blank: batteries, no C-wire (smart stats), blown 3/5 A fuse, float switch, transformer.
- Test the equipment with jumpers at the board: R–G = fan, R–Y + R–G = cooling, R–W = heat. Works = thermostat or its wire.
- Wrong mode/config: heat pump vs conventional, O/B, number of stages, compressor delay.
- Reads wrong temp: bad location (sun, supply air, outside wall, hole behind stat letting wall air in, so seal it).
- Loose wire at the stat or board causes random short cycling.
Mini-split basicsDuctless
- Error codes: read on the indoor unit display, remote or blinking LEDs. Look them up in that model's service manual; codes differ by brand and series.
- Comm wire: many systems power the indoor unit and talk over the same interconnect (e.g. S1-S2-S3). Use the cable the maker specifies, no splices, correct terminal order. Comm faults are often wiring or loose terminals.
- Inverter board caution: DC bus capacitors can hold several hundred volts DC for minutes after power off. Wait, then verify 0 V DC before touching. Never megger through an inverter board.
- Inverter compressors don't use run caps or contactors; diagnose with the maker's checks (winding ohms between U-V-W should match).
- Charge by weight per the manual (adjust for line length); SH/SC readings vary with inverter speed.
- Clean indoor coil and blower wheel: dirty wheels cause low airflow, spitting water and odors.
IAQ / mold quick notesIAQ
- Mold on coil, pan or grilles = moisture problem first: humidity, drain, sweating ducts. Fix that before cleaning.
- Clean with coil cleaner approved for indoor coils; no bleach on aluminum coils.
- Higher MERV filters catch more but add static. Check static before upsizing.
- UV lights on the coil help keep the coil/pan clean; mount to the maker's instructions (UV can degrade plastics and wiring).
- Visible mold on ductwork or drywall: refer to a mold remediation pro.
Florida-specific notesFL
- Salt air: near the coast, condenser coils and cabinets corrode fast. Rinse coils with fresh water (low pressure), consider coated coils and stainless hardware, inspect fins and U-bends for leaks.
- Lightning / surge: after storms check the low-voltage fuse, boards, transformer and contactor coil. Recommend surge protection at the condenser and panel.
- Condensate algae: the #1 FL service call. Trap, cleanout tee, regular flushing and drain treatment; float switch on every system.
- High humidity: set airflow near 350 CFM/ton or use dehumidify mode, fan on AUTO, right-size equipment.
- Hurricanes / floods: don't power up a unit that was underwater until it's inspected. Check pad level and hurricane straps.
- Bugs and critters: ants and lizards in contactors cause no-cool calls; clean and check the contacts.
- Attic heat: air handlers in hot attics: insulate lines and ducts well, check for sweating and leaks.
Safety & disclaimer
- For trained, qualified HVAC technicians. Homeowners: call us at Douglas HVAC Mechanical instead of opening equipment.
- Lock out / tag out. Verify 0 V before touching terminals. Capacitors hold a charge; discharge them safely.
- Refrigerant handling requires EPA Section 608 certification. Recover, never vent. Use the right gauges/hoses for the refrigerant.
- R-454B and R-32 are A2L (mildly flammable): A2L-rated recovery machines and tools, ventilation, no open flame near leaks.
- The manufacturer's charging chart, specs, wiring diagram and local codes always come before these rules of thumb.
- Results are estimates to help diagnosis and are given without warranty.
Data sources
- R-410A, R-32, R-22 saturation tables: NIST-based equations of state (CoolProp), checked against the Chemours "Pressure-Temperature Guide for A/C" (OPTXLPTAC, 2025).
- R-454B bubble/dew: Chemours "Thermodynamic Properties of Opteon XL41" data (−40 to 150°F).
- Wire ampacity: NEC Table 310.16; NEC 110.14(C), 240.4(G), Article 440.